Ex n floodlights for high pressure sodium lamps or metal halide lamps are applicable for zone 2 areas. The floodlights are produced with deep drawn seamless steel housing and have a very high light output. No tools are required to open the housing.
The Floodlights are designed to meet maritime requirements.
Mounting
1776 001-002 / 1776 073-074:
Adjustable bracket, stainless steel 316, unpainted with 5 holes, Ø 10.5 / 14 mm
1776 060-066 / 1776 005-028:
2 adjustable brackets, stainless steel 316, unpainted with 2 mounting holes each, Ø 14 mm
Electric
1776 001-002 / 1776 073-074:
Flexible wiring, silicone insulated, heat resistant up to 180° C, exterior connection box; terminal 3 - pole / 6 mm².
1776 060-066:
Flexible wiring, silicone insulated, heat resistant up to 180° C, 2 exterior connection boxes with 1 ignition unit each; terminal 3 - pole / 6 mm².
1776 005-028:
Flexible wiring, silicone insulated, heat resistant up to 180° C, exterior connection box with ignition unit, ballast incorporated; terminal 3 - pole / 6 mm².
Housing
Housing made of stainless steel AISI316 deep drawn and powder coated white RAL 9016.
Special colours available on request.
Lightsource/Optic
The floodlight is available for different light sources with E40 lamp holder:
1776 001-002:
(Not included.) High pressure sodium lamps (HS ) / metal halide lamps (HI).
1776 073-074:
(not included) Halogen lamp 500W
1776 060-066:
(Not included.) High pressure sodium lamps (HS ) / metal halide lamps (HI)
1776 005-028:
(Not included.) High pressure sodium lamps (HS ) / metal halide lamps (HI)
Aluminium reflector in Wide (WB) or Narrow beam (NB) covered by a safty glass pane gives a high light output.
Remarks
Ballast unit has to be ordered separatly for floodlights without incorporated ballast. See type no 1527. Use lamps from well known manufactures only.
Application
Hazardous areas zone 2
Design
According to international rules for zone 2 and EN 50021:1999 / IEC 79-15, EN 60079-15:2005
Ambient Temperature
- 20° C up to + 55° C
Finish
Powder coated white RAL 9016 and enamelled up to 70 - 80 μm thickness.
Pane
Safety glass
Cable entry
Brass cable gland M 24 x 1.5 MGCG; standard for cable dia. 10 to 12.5 mm.